How to Select a Circulation Pump for Underfloor Heating: Flow, Head & Control Modes

A practical hydronic underfloor heating (UFH) pump-selection guide for installers, distributors and project buyers.

Quick answer (BLUF): Size a UFH circulator at the total simultaneous design flow and the head loss of the most resistant complete flow path. For a water-based system, flow depends on heat load and supply–return temperature difference (ΔT); pump head depends on pipe, manifold, valve and heat-exchanger resistance. In a properly filled closed loop, do not add the building height as permanent circulation head. For manifold circuits with zone actuators, constant differential-pressure control is a useful starting point, subject to the actual hydraulic design. Match both values to a model-specific pump curve—not to maximum flow or maximum head alone.

1. What information is needed before choosing the pump?

A heating area in square metres is not enough to specify a circulator. Ask for the calculated design heat load (kW), supply and return design temperatures, number and lengths of loops, pipe internal diameter, manifolds and control valves, water or glycol concentration, and whether the heat source already has a suitable pump. Confirm the hydraulic boundary of the new circulator: a dedicated UFH mixing manifold circuit is different from a whole-building primary circuit.

Design inputWhat it changesBuyer action
Design heat load (kW)Required heat carried by circulating waterRequest room-by-room heating design, not area alone
Supply/return ΔT (K)Required flow at the same heat loadObtain the selected design temperatures
Active loop flowsTotal simultaneous manifold flowSum flows of loops expected to be open together
Index-circuit pressure lossCirculator head at design flowGet loop, shared pipe, manifold and valve losses
Control valves / actuatorsFlow and head behavior at part loadSpecify differential-pressure control requirement
Heat source / fluidMinimum flow, viscosity and temperature limitsConfirm boiler/heat pump circuit arrangement and antifreeze specification

2. Worked example: calculate UFH circulation flow

For water only, a convenient engineering approximation is:

Flow (m³/h) ≈ Design heat load (kW) ÷ [1.163 × ΔT (K)]

Suppose a project requires 8.0 kW of space-heating output at a 5 K design temperature difference. The estimated full-load flow is 8 ÷ (1.163 × 5) = 1.38 m³/h, or about 22.9 L/min. If the design has six equal-load loops, each would average about 3.82 L/min; actual loop settings must follow each room’s heat-loss calculation and pipe design.

Illustrative design inputValueMeaning
Space-heating load8.0 kWHypothetical building design load
Supply/return temperature difference5 KDesign assumption; not a universal UFH setting
Water-only design flow1.38 m³/h (22.9 L/min)Sum of simultaneous circuit flows
Number of active loops6Example, not a recommended loop count
Average flow per loop3.82 L/minEqual-load illustration only

Important: Water with glycol requires different density, viscosity and heat-capacity assumptions. Do not use the simple water coefficient without checking the actual fluid. Also confirm that the manifold, loop lengths and flowmeters can accommodate the computed flow.

3. Calculate pump head from the index loop—not the floor height

The circulator must overcome pressure loss along the most hydraulically demanding complete path at the design flow. In a parallel-loop manifold, do not add the pressure drops of all parallel loops together. Instead, add losses along the worst loop and the shared supply/return components that its flow passes through.

Assumed pressure-loss componentPressure lossPath treatment
Most resistant UFH loop (supply + return)18 kPaOne index loop, not all six loops
Manifold, mixing/control valve and fittings8 kPaComponents in that path
Shared distribution pipework5 kPaSupply/return sections included once
Total differential pressure31 kPaIllustrative design head
Equivalent water head31 ÷ 9.81 ≈ 3.16 mApproximation using water density near 1000 kg/m³

The illustrative pump duty point is therefore 1.38 m³/h at about 3.16 m head. A specific pump can be selected only after checking its published Q–H curve at the intended control mode and speed. A 6 m or 8 m maximum-head label alone does not prove that it delivers 1.38 m³/h at 3.16 m.

In a properly filled, pressurised closed heating loop, water rises and returns through the same circuit, so static elevation generally cancels as a continuous pump-head requirement. Building height still matters for system fill pressure, air removal and pressure rating; open or hydraulically separated circuits require their own analysis.

4. Constant pressure vs proportional pressure vs fixed speed

The optimum control mode depends on how loop actuators and valves change the network’s resistance. These are commissioning starting points—not universal settings.

ModeWhat the pump doesTypical decision pointWhat to verify
Constant differential pressureAdjusts speed to hold a chosen head as zone valves open or closeOften a good first choice for UFH manifolds with zone actuatorsLoop flowmeters, pressure noise, system balancing and minimum source flow
Proportional differential pressureReduces target head as total flow fallsConsider networks with significant shared pipe friction or mixed radiator circuitsRemote-loop flow and differential pressure at part load
Fixed speed / selected curveRuns on a selected speed curve; head changes with flowSimple stable-flow circuits or manufacturer-specified operationAvoid excess differential pressure and unnecessary pumping power
AUTO / adaptiveUses product-specific automatic logicUseful only where supported and commissioning confirms correct flowActual mode behavior and low-demand operation
PWM inputExternal compatible controller commands pump behaviorWhere the heating controller and exact pump option support PWMSignal standard, wiring, fail-safe setting and model variant

5. Which Stream EA or A circulation pump should buyers check?

Stream publishes two variable-speed circulator product families relevant to hydronic heating. The values below are published series ranges across variants; the endpoints are not simultaneous operating points.

Stream seriesOfficial published series dataControl informationSelection note
SXR-EA high-efficiency circulator230 V, 50/60 Hz; 25–80 W; maximum-head range 4–10 m; maximum-flow range 36–66 L/min; liquid 2–110°CAUTO, fixed speed, constant pressure, proportional pressure; PWM is an available optionVerify exact variant, Q–H curve, pump length, connection and PWM availability
SXR-A advanced circulator230 V, 50/60 Hz; 22–68 W; maximum-head range 4–8 m; maximum-flow range 40–78 L/min; liquid 2–110°CAUTO, fixed speed, constant pressure, proportional pressure, night mode; LED displayVerify selected speed/head curve and control settings
Manufacturer control-mode overviewEA / A / E product introductionPublished launch article explains mode differencesDo not assume all modes are available on every individual SKU

Both EA and A product pages also list a maximum system pressure of 1 MPa, IP44 protection and an EEI statement of ≤0.23. These are manufacturer-published specifications, not independently verified product test results here. Request the exact SKU datasheet and any required market-specific documents before ordering.

6. Commissioning and troubleshooting checklist

  • Verify topology: identify whether an existing boiler/heat-pump pump already serves the circuit and whether hydraulic separation is required.

  • Verify design flow: balance each manifold circuit to the room load; do not set all loops to an arbitrary identical rate.

  • Verify differential head: compare calculated index-circuit resistance with the chosen pump curve.

  • Protect the heat source: respect its specified minimum flow even when zone actuators close; provide the hydraulic arrangement required by the appliance designer.

  • Check fluid and hardware: temperature, glycol, connection size, installation length, orientation, system pressure and suitable electrical supply.

  • Commission control mode: start from the system designer’s specified mode, then check real flowmeters, temperature difference, noise and operation when only a few zones call for heat.

  • Document the result: record chosen SKU, control setting, operating point, manifold readings and changes made during balancing.

7. What to send Stream for a UFH circulation pump quotation

Send the heat load (kW), selected ΔT, design flow (L/min or m³/h), index-loop pressure loss (kPa or m), system diagram, number of manifold loops, pipe and fitting details, maximum liquid temperature, glycol percentage, voltage/frequency, installation length and preferred control mode. Ask for the model-specific pump curve at that mode, dimensional drawing and confirmation of included functions. Contact Stream Pumps with the completed duty point.

Frequently asked questions

Is a 6 m circulation pump always suitable for underfloor heating?

No. The 6 m label usually refers to maximum head at a particular condition, not the head available at the required design flow. Check the Q–H curve at your duty point.

Does a two-storey UFH installation need twice the circulation head?

Not automatically. In a closed, filled circuit, static height does not simply add to continuous pumping head. Pipe friction, manifold losses and the critical flow path govern the circulating duty. Filling pressure must still be assessed separately.

Should I always choose constant pressure for UFH?

No. Constant differential pressure is a useful starting point for many manifold systems with actuators, but proportional pressure, fixed speed or a designed control scheme may be more suitable when shared pipework, minimum flow or hydraulic topology differs.

Can I select a pump from heating area alone?

Area alone is insufficient. Start with a room-by-room heating load, design water-temperature difference, actual loop lengths and pressure losses.

Conclusion

For a water-based underfloor heating circuit, select the circulation pump at design flow and index-loop pressure loss, then commission an appropriate differential-pressure mode. The example above arrives at 1.38 m³/h at approximately 3.16 m, but it is an illustrative engineering calculation, not a Stream model recommendation. Review Stream SXR-EA and SXR-A using their individual performance curves before procurement.

Technical basis and transparency: General closed-loop hydronic sizing and system losses: ASHRAE Handbook — Hydronic Heating and Cooling. Circulator scope and efficiency context: European Commission — Circulators. Stream series capabilities: SXR-EA product page, SXR-A product page and EA/A/E mode overview. All numerical design inputs in the calculation example are hypothetical; no laboratory testing, field measurement, independent certification or project-specific performance is claimed.