How to Select a Circulation Pump for Underfloor Heating: Flow, Head & Control Modes
A practical hydronic underfloor heating (UFH) pump-selection guide for installers, distributors and project buyers.
1. What information is needed before choosing the pump?
A heating area in square metres is not enough to specify a circulator. Ask for the calculated design heat load (kW), supply and return design temperatures, number and lengths of loops, pipe internal diameter, manifolds and control valves, water or glycol concentration, and whether the heat source already has a suitable pump. Confirm the hydraulic boundary of the new circulator: a dedicated UFH mixing manifold circuit is different from a whole-building primary circuit.
| Design input | What it changes | Buyer action |
|---|---|---|
| Design heat load (kW) | Required heat carried by circulating water | Request room-by-room heating design, not area alone |
| Supply/return ΔT (K) | Required flow at the same heat load | Obtain the selected design temperatures |
| Active loop flows | Total simultaneous manifold flow | Sum flows of loops expected to be open together |
| Index-circuit pressure loss | Circulator head at design flow | Get loop, shared pipe, manifold and valve losses |
| Control valves / actuators | Flow and head behavior at part load | Specify differential-pressure control requirement |
| Heat source / fluid | Minimum flow, viscosity and temperature limits | Confirm boiler/heat pump circuit arrangement and antifreeze specification |
2. Worked example: calculate UFH circulation flow
For water only, a convenient engineering approximation is:
Suppose a project requires 8.0 kW of space-heating output at a 5 K design temperature difference. The estimated full-load flow is 8 ÷ (1.163 × 5) = 1.38 m³/h, or about 22.9 L/min. If the design has six equal-load loops, each would average about 3.82 L/min; actual loop settings must follow each room’s heat-loss calculation and pipe design.
| Illustrative design input | Value | Meaning |
|---|---|---|
| Space-heating load | 8.0 kW | Hypothetical building design load |
| Supply/return temperature difference | 5 K | Design assumption; not a universal UFH setting |
| Water-only design flow | 1.38 m³/h (22.9 L/min) | Sum of simultaneous circuit flows |
| Number of active loops | 6 | Example, not a recommended loop count |
| Average flow per loop | 3.82 L/min | Equal-load illustration only |
Important: Water with glycol requires different density, viscosity and heat-capacity assumptions. Do not use the simple water coefficient without checking the actual fluid. Also confirm that the manifold, loop lengths and flowmeters can accommodate the computed flow.
3. Calculate pump head from the index loop—not the floor height
The circulator must overcome pressure loss along the most hydraulically demanding complete path at the design flow. In a parallel-loop manifold, do not add the pressure drops of all parallel loops together. Instead, add losses along the worst loop and the shared supply/return components that its flow passes through.
| Assumed pressure-loss component | Pressure loss | Path treatment |
|---|---|---|
| Most resistant UFH loop (supply + return) | 18 kPa | One index loop, not all six loops |
| Manifold, mixing/control valve and fittings | 8 kPa | Components in that path |
| Shared distribution pipework | 5 kPa | Supply/return sections included once |
| Total differential pressure | 31 kPa | Illustrative design head |
| Equivalent water head | 31 ÷ 9.81 ≈ 3.16 m | Approximation using water density near 1000 kg/m³ |
The illustrative pump duty point is therefore 1.38 m³/h at about 3.16 m head. A specific pump can be selected only after checking its published Q–H curve at the intended control mode and speed. A 6 m or 8 m maximum-head label alone does not prove that it delivers 1.38 m³/h at 3.16 m.
In a properly filled, pressurised closed heating loop, water rises and returns through the same circuit, so static elevation generally cancels as a continuous pump-head requirement. Building height still matters for system fill pressure, air removal and pressure rating; open or hydraulically separated circuits require their own analysis.
4. Constant pressure vs proportional pressure vs fixed speed
The optimum control mode depends on how loop actuators and valves change the network’s resistance. These are commissioning starting points—not universal settings.
| Mode | What the pump does | Typical decision point | What to verify |
|---|---|---|---|
| Constant differential pressure | Adjusts speed to hold a chosen head as zone valves open or close | Often a good first choice for UFH manifolds with zone actuators | Loop flowmeters, pressure noise, system balancing and minimum source flow |
| Proportional differential pressure | Reduces target head as total flow falls | Consider networks with significant shared pipe friction or mixed radiator circuits | Remote-loop flow and differential pressure at part load |
| Fixed speed / selected curve | Runs on a selected speed curve; head changes with flow | Simple stable-flow circuits or manufacturer-specified operation | Avoid excess differential pressure and unnecessary pumping power |
| AUTO / adaptive | Uses product-specific automatic logic | Useful only where supported and commissioning confirms correct flow | Actual mode behavior and low-demand operation |
| PWM input | External compatible controller commands pump behavior | Where the heating controller and exact pump option support PWM | Signal standard, wiring, fail-safe setting and model variant |
5. Which Stream EA or A circulation pump should buyers check?
Stream publishes two variable-speed circulator product families relevant to hydronic heating. The values below are published series ranges across variants; the endpoints are not simultaneous operating points.
| Stream series | Official published series data | Control information | Selection note |
|---|---|---|---|
| SXR-EA high-efficiency circulator | 230 V, 50/60 Hz; 25–80 W; maximum-head range 4–10 m; maximum-flow range 36–66 L/min; liquid 2–110°C | AUTO, fixed speed, constant pressure, proportional pressure; PWM is an available option | Verify exact variant, Q–H curve, pump length, connection and PWM availability |
| SXR-A advanced circulator | 230 V, 50/60 Hz; 22–68 W; maximum-head range 4–8 m; maximum-flow range 40–78 L/min; liquid 2–110°C | AUTO, fixed speed, constant pressure, proportional pressure, night mode; LED display | Verify selected speed/head curve and control settings |
| Manufacturer control-mode overview | EA / A / E product introduction | Published launch article explains mode differences | Do not assume all modes are available on every individual SKU |
Both EA and A product pages also list a maximum system pressure of 1 MPa, IP44 protection and an EEI statement of ≤0.23. These are manufacturer-published specifications, not independently verified product test results here. Request the exact SKU datasheet and any required market-specific documents before ordering.
6. Commissioning and troubleshooting checklist
Verify topology: identify whether an existing boiler/heat-pump pump already serves the circuit and whether hydraulic separation is required.
Verify design flow: balance each manifold circuit to the room load; do not set all loops to an arbitrary identical rate.
Verify differential head: compare calculated index-circuit resistance with the chosen pump curve.
Protect the heat source: respect its specified minimum flow even when zone actuators close; provide the hydraulic arrangement required by the appliance designer.
Check fluid and hardware: temperature, glycol, connection size, installation length, orientation, system pressure and suitable electrical supply.
Commission control mode: start from the system designer’s specified mode, then check real flowmeters, temperature difference, noise and operation when only a few zones call for heat.
Document the result: record chosen SKU, control setting, operating point, manifold readings and changes made during balancing.
7. What to send Stream for a UFH circulation pump quotation
Send the heat load (kW), selected ΔT, design flow (L/min or m³/h), index-loop pressure loss (kPa or m), system diagram, number of manifold loops, pipe and fitting details, maximum liquid temperature, glycol percentage, voltage/frequency, installation length and preferred control mode. Ask for the model-specific pump curve at that mode, dimensional drawing and confirmation of included functions. Contact Stream Pumps with the completed duty point.
Frequently asked questions
Is a 6 m circulation pump always suitable for underfloor heating?
No. The 6 m label usually refers to maximum head at a particular condition, not the head available at the required design flow. Check the Q–H curve at your duty point.
Does a two-storey UFH installation need twice the circulation head?
Not automatically. In a closed, filled circuit, static height does not simply add to continuous pumping head. Pipe friction, manifold losses and the critical flow path govern the circulating duty. Filling pressure must still be assessed separately.
Should I always choose constant pressure for UFH?
No. Constant differential pressure is a useful starting point for many manifold systems with actuators, but proportional pressure, fixed speed or a designed control scheme may be more suitable when shared pipework, minimum flow or hydraulic topology differs.
Can I select a pump from heating area alone?
Area alone is insufficient. Start with a room-by-room heating load, design water-temperature difference, actual loop lengths and pressure losses.
Conclusion
For a water-based underfloor heating circuit, select the circulation pump at design flow and index-loop pressure loss, then commission an appropriate differential-pressure mode. The example above arrives at 1.38 m³/h at approximately 3.16 m, but it is an illustrative engineering calculation, not a Stream model recommendation. Review Stream SXR-EA and SXR-A using their individual performance curves before procurement.